Branch Pipe
Main Pipe
Distributor
Distributor
B
B
h2
Multi Piping Type Distributor Type
Installation of Indoor, Outdoor Unit
Installation Manual 7
ENGLISH
Multi Piping Type (m)
Distributor Type (m)
Piping length and elevation
14k/16k 30 20 15 7.5
18k 40 25 15 7.5
24k 50 25 15 7.5
30k 70 25 15 7.5
Capacity(Btu/h) Total Length Max Length(A/B)
Max Elevation
(h1)
In - In Elevation
(h2)
40k 100 50 50 15 30 10
48k 110 50 60 15 30 10
56k 120 50 70 15 30 10
Capacity
(Btu/h)
Total Length
Max Main Pipe
Length (A/B)
Total Branch
Pipe Length
Max Branch
Pipe Length
Max Elevation
(h1)
In - In Elevation
(h2)
CAUTION: Capacity is based on standard length and maximum allowance
length is on the basis of reliability. Oil trap should be installed every 5~7
meters.