www.lg.comPlease read this installation manual completely before installing the product.Installation work must be performed in accordance with the nat
Standard drawing of installation10 VentilatorLZ-H050GXH0 / LZ-H080GXH0 / LZ-H100GXH0CBAModelLZ-H050GXH0LZ-H080GXH0LZ-H100GXH0[Unit : mm]Duct slope: Mo
InstallationInstallation Manual 11ENGLISHInstallationSelection of the best locationRead completely, then follow step by step.Install the ventilator i
Installation12 Ventilatorn Installation of UnitInstall the unit above the ceiling correctly.• Apply a Flexible duct between the unit and duct to absor
InstallationInstallation Manual 13ENGLISH• Select and mark the position for fixing bolts.• Drill the hole for set anchor on the face of ceiling.• Ins
Installation14 VentilatorDrain holeDrain hole Duct connecting FlangeHorizontal line1 degree or less 1 degree or less• Attach the hanger bracket to the
Drain Piping and Water Supply WorkInstallation Manual 15ENGLISH100 mmor moreCentral drain piping (Install with a downward slope of at least 1/100)• K
Drain Piping and Water Supply Work16 Ventilator• Test the drainage by pouring 1000cc of water into the drain pan through the inspection hole by remov-
Drain Piping and Water Supply WorkInstallation Manual 17ENGLISH• After checking that the drain piping connections do no leakage, insulate them using
18 VentilatorDuct ConnectionDuct Connection• The change of air discharge grill’s location should be examined when the cold draft from air dis-charge
Installation Manual 19ENGLISHConnecting PipesMain cause of gas leakage is defect in flaringwork. Carry out correct flaring work in the follow-ing pro
2 VentilatorVentilator Installation ManualTABLE OF CONTENTSSafety Precaution...3Introduction ...8Feature Dimensio
20 VentilatorConnecting PipesConnecting the pipings to the indoor unit and drain hose to drain pipeInsulation, Others• Align the center of the pipings
Installation Manual 21ENGLISHWire SpecificationPower Cable Specification : The power cordconnected to the outdoor unit should be com-plied with IEC 6
22 VentilatorWiring ConnectionMake sure that the screws of the terminal are free from looseness.WARNING Connecting Cable Specification : The connectin
Wiring ConnectionInstallation Manual 23ENGLISHMethod to Connect WiringMake sure that the screws of the terminal are free from looseness.WARNING1(A)2(
24 VentilatorWiring ConnectionMotorDriverPCBTerminal Block 2Sub PCBMain PCBTerminal Block 1PowerSupplyWiringRemoteControllerWiringAdditionalPartsWirin
Installation Manual 25ENGLISHWiring ConnectionWiring for the Humidity Regulator (Locally Procured)<LZ-H***GXH series only>1. Pass into the elec
26 VentilatorWiring Example• This unit can be used as part of the combined operation system used together with indoor units(Multi-V system air conditi
Field Setting and Test RunInstallation Manual 27ENGLISH1. Function Explanation- After installation by the installer, it performs the function for pro
28 VentilatorInstaller Setting Code and Value Table Test Run1. Function explanation: when installing the product, test operation for checking the ins
Installation Manual 29ENGLISHField Setting and Test Run Supply/Exhaust ESP setting1. Function explanation: Set the E.S.P(RPM) value of air condition
Safety Precautions Installation Manual 3ENGLISHSafety PrecautionsTo prevent injury to the user or other people and property damage, the following i
30 Ventilator Zone Stats1. Function explanation: Set the wind strength option of indoor unit as Variable or fixed. 2. Function control and setting2.1
Installation Manual 31ENGLISHField Setting and Test RunRun the humidifier<LZ-H***GXH series only>(1) Check that the water supply piping is conn
32 VentilatorIn case of finding a problem at a trial operationThe Product doesn't workThe Product doesn't work throughyou press the 'ON
Safety Precautions 4 VentilatorFor installation, alwayscontact the dealer oran Authorized ServiceCenter.• There is risk of fire,electric shock, expl
Safety Precautions Installation Manual 5ENGLISHInstall this product inand environmentswhere the outside airintake meets the fol-lowing conditions:t
Safety Precautions 6 VentilatorCAUTIONDon't connect theground wire to the win-dow frame or watercock. • There is risk of electricshock.Do not i
Safety Precautions Installation Manual 7ENGLISHKeep level even wheninstalling the prod-uct. • To avoid vibration orwater leakage.Use two or more pe
Introduction 8 VentilatorApplication tools(CMH)IntroductionFeature Dimension DiagramModel : LZ-H050GXN0, LZ-H080GXN0, LZ-H100GXN0LZ-H050GXH0, LZ-H080G
Standard drawing of installationInstallation Manual 9ENGLISHStandard drawing of installationLZ-H050GXN0 / LZ-H080GXN0 / LZ-H100GXN0CBAModelLZ-H050GXN